In dry places for wiring inside buildings and panels when more flexibility is needed, these new wires are used for installing inside electrical appliances and protecting lighting systems in dry environments,
inside pipes, under and on plaster in pipes. hoses are suitable
It is not allowed to place these types of wires directly on cable trays, channels or tanks, but it is allowed to place them inside the pipe and under the plaster.
Conductor: Group 5 annealed copper (flexible)
Insulation: PVC of PVC/C type
Nominal voltage: 450/750V
Standard:
• ISIRI 607-3 is the international equivalent of IEC 60227-3
Wire code:
• ISIRI (607) 06 for conductors up to 1mm²
• IEC 60227 06 (H05V-K)
• ISIRI (607) 02 for conductors with a cross section greater than 1mm²
• IEC 60227 02 (H07V-K)
Temperature range:
For flexible installation: -5℃ to +70℃
For fixed installation: -30℃ to +70℃
Approximate weight
|
Maximum conductor resistance
|
Average maximum final diameter
|
Average minimum final diameter
|
Nominal thickness of insulation
|
Nominal cross-sectional area of the conductor
|
Kg\km | 20درجه سانتیگراد | mm | mm | mm | mm² |
8.5 | 39 | 2.5 | 2.1 | 0.6 | 0.5 |
11.5 | 26 | 2.7 | 2.2 | 0.6 | 0.75 |
14.5 | 19.5 | 2.8 | 2.4 | 0.6 | 1 |
20.5 | 13.3 | 3.4 | 2.8 | 0.7 | 1.5 |
31 | 7.98 | 4.1 | 3.4 | 0.8 | 2.5 |
45.5 | 4.95 | 4.8 | 3.9 | 0.8 | 4 |
64.8 | 3.3 | 5.3 | 4.4 | 0.8 | 6 |
109 | 1.91 | 6.8 | 5.7 | 1 | 10 |
164 | 1.21 | 8.1 | 6.7 | 1 | 16 |
252 | 0.78 | 10.2 | 8.4 | 1.2 | 25 |
343 | 0.554 | 11.7 | 9.7 | 1.2 | 35 |
490 | 0.386 | 13.9 | 11.5 | 1.4 | 50 |
679 | 0.272 | 16 | 13.2 | 1.4 | 70 |
894 | 0.206 | 18.2 | 15.1 | 1.6 | 95 |
1128 | 0.161 | 20.2 | 16.7 | 1.6 | 120 |
1409 | 0.129 | 22.5 | 18.6 | 1.8 | 150 |
1712 | 0.106 | 24.9 | 20.6 | 2 | 185 |
2256 | 0.0801 | 28.4 | 23.5 | 2.2 | 240 |