In dry places for wiring inside buildings and panels when more flexibility is needed, these new wires are used for installing inside electrical appliances and protecting lighting systems in dry environments, 
inside pipes, under and on plaster in pipes. hoses are suitable It is not allowed to place these types of wires directly on cable trays, channels or tanks, but it is allowed to place them inside the pipe and under the plaster.
Conductor: Group 5 annealed copper (flexible)
Insulation: PVC of PVC/C type
Nominal voltage: 450/750V
Standard:
• ISIRI 607-3 is the international equivalent of IEC 60227-3
Wire code:
• ISIRI (607) 06 for conductors up to 1mm²
• IEC 60227 06 (H05V-K)
• ISIRI (607) 02 for conductors with a cross section greater than 1mm²
• IEC 60227 02 (H07V-K)

Temperature range:
For flexible installation: -5℃ to +70℃
For fixed installation: -30℃ to +70℃
Approximate weight
Maximum conductor resistance

 
Average maximum final diameter

 
Average minimum final diameter

 
Nominal thickness of insulation

 
Nominal cross-sectional area of ​​the conductor

 
Kg\km 20درجه سانتیگراد mm mm mm mm²
8.5 39 2.5 2.1 0.6 0.5
11.5 26 2.7 2.2 0.6 0.75
14.5 19.5 2.8 2.4 0.6 1
20.5 13.3 3.4 2.8 0.7 1.5
31 7.98 4.1 3.4 0.8 2.5
45.5 4.95 4.8 3.9 0.8 4
64.8 3.3 5.3 4.4 0.8 6
109 1.91 6.8 5.7 1 10
164 1.21 8.1 6.7 1 16
252 0.78 10.2 8.4 1.2 25
343 0.554 11.7 9.7 1.2 35
490 0.386 13.9 11.5 1.4 50
679 0.272 16 13.2 1.4 70
894 0.206 18.2 15.1 1.6 95
1128 0.161 20.2 16.7 1.6 120
1409 0.129 22.5 18.6 1.8 150
1712 0.106 24.9 20.6 2 185
2256 0.0801 28.4 23.5 2.2 240
Your rating to this product
whatsapp