Single strand aluminum power cables with PVC insulation and coating

from 0 Vote
  • Available
  • Ability to send immediately
Call
Application :
These types of cables are used for supplying electric energy, outdoors, underground, under water, inside buildings, cable channels, power plants, industrial uses,
in distribution centers and consumption networks, and in places where there is a possibility of mechanical damage to the cable. It does not exist. Cable layers: Cu/PVC/PVC Cu/XLPE/PVC Cu/XLPE/PE Cu/XLPE/LSZH Al/PVC/PVC Al/XLPE/PVC Al/XLPE/PE Al/XLPE/LSZH

Community Verified icon
 
 
 
 
Rated voltage :

0.6/1 KV 
Standard :

ISIRI 3569 – 1
IEC 60502 – 1

Cable code:

NYY

N2XY
N2X2Y
NAYY
NA2XY
NA2X2Y

Temperature range:

PVC insulation: from -30℃ to +70℃

 
XLPE insulation: from -40℃ to +90℃

 
Approximate weight
Maximum conductor resistance

 
Average maximum final diameter

 
Nominal coating thickness

 
Nominal thickness of insulation

 
Conductor class

 
Nominal cross section of the conductor

 
Kg\km Ω/km mm² mm mm   mm²
94 3.08 8.7 1.4 1 1 10
121 1.91 9.7 1.4 1 2 16
169 1.2 11.4 1.4 1.2 2 25
207 0.868 12.5 1.4 1.2 2 35
285 0.641 14.7 1.4 1.4 2 50
369 0.443 16.4 1.4 1.4 2 70
502 0.32 19.4 1.5 1.6 2 95
607 0.253 20.7 1.5 1.6 2 120
716 0.206 22.6 1.6 1.8 2 150
879 0.164 25.8 1.7 2 2 185
1120 0.125 28.4 1.8 2.2 2 240
1393 0.1 31.8 1.9 2.4 2 300
1736 0.0778 1634.7 2 2.6 2 400
2144 0.0605 39.5 2.1 2.8 2 500
Your rating to this product
whatsapp